Chapter 4: AC Drive Parameters
Page 4–141
DURApulse GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
Type Hex Addr Dec Addr
P6.30 Heat Sink OH Warning Level
♦R/W 061E 41567
Range/Units (Format: 16-bit unsigned) Default
0�0~110�0 °C
105�0
This parameter sets the temperature at which a warning will occur for heat sink monitoring.
If this parameter is set at 110.0°C and the GS4 drive temperature reaches 110.0°C, the drive will
trigger an error and stop, instead of just warning. The heat sink FAULT level is 110°C and cannot be
changed.
For Frame C and above, when IGBT temperature reaches (P6.30 setting minus 15°C), the heatsink
fan will accelerate to the highest speed. When IGBT temperature is lower than (P6.30 setting
minus 35°C), and capacitor temperature is lower than (OH2 capacitor warning level minus 10°C),
the heatsink fan will return to its setting speed.
If this parameter is set lower than 35°C, the level will remain at 35°C.
IGBT and Capacitor Over-Heat Fault Levels* (°C)
Model #
(230V)
Frame
Size
OH1 OH2
Model #
(460V)
Frame
Size
OH1 OH2
IGBT Capacitor IGBT Capacitor
CT & VT* CT* VT* CT & VT* CT* VT*
GS4-21P0
A
110
95 90 GS4-41P0
A
110
95 90
GS4-22P0
100 95
GS4-42P0 100 95
GS4-23P0 GS4-43P0 105 100
GS4-25P0 GS4-45P0
100 95GS4-27P5
B
GS4-47P5
GS4-2010
80 75
GS4-4010
BGS4-2015 GS4-4015
105
80 75GS4-2020
C
GS4-4020
GS4-2025
105
GS4-4025
CGS4-2030 GS4-4030
85 80
GS4-2040
D
75 70 GS4-4040
GS4-2050
65 55
GS4-4050
D0
110
GS4-2060
E
GS4-4060
105
65 55
GS4-2075
110
GS4-4075
D
GS4-2100 GS4-4100
GS4-4125
E
110
GS4-4150
GS4-4175
F
GS4-4200
GS4-4250
G
GS4-4300 70 60
* The over heating warning levels for OH1 and OH2 are 5°C less than the listed
fault temperatures.
CT = Constant Torque (normal duty).
VT = Variable Torque (light duty).
Related parameters: P6.39 & P6.40 determine the Motor Overheating Level (OH3)

Table of Contents

Other manuals for Automation Direct DURApulse GS4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Automation Direct DURApulse GS4 and is the answer not in the manual?

Automation Direct DURApulse GS4 Specifications

General IconGeneral
BrandAutomation Direct
ModelDURApulse GS4
CategoryController
LanguageEnglish

Related product manuals