Page #272 background image
Page 4–178
DURApulse GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
Chapter 4: AC Drive Parameters
Type Hex Addr Dec Addr
P8.07 Password Set Up
♦ R/W 0807 42056
Range/Units (Format: 16-bit unsigned) Default
0~65535
0
This parameter sets up a password to protect parameter settings from unauthorized
modifications. For the first set up, enter a password of your choice. When finished entering the
password, the setting of parameter P8.07 will be 1. Then password protection is activated. All
parameters will display a value of 0 when locked. If you want to modify any parameter, go to
parameter P8.06, enter the password that you set up here. Then you can modify the parameter. If
all parameters are locked and P8.07 reads a 0, then P9.08 is most likely set to 1.
Password setting is permanently effective. If you need to modify any parameter, decode the
parameter protection at Parameter P8.06.
To disable the password lock set first enter the currect password in P8.06, then set P8.07 = 0.
Password protection will remain off even during power cycles until a new password is set up.
If you would like a new password you must first enter your old password to unlock the drive, then
enter a new password in P8.07 and press enter. The drive parameter protection is now locked with
the new password in effect.
How to re-start the parameter protection after the password is decoded:
Method 01: Cycle power to the GS4 drive to restore the password protection if set�
Method 02: Input any value into P8�06 (Do not enter the correct password)�
Password Setting
P8.07
Displays 01 after
correct password is
entered to P8.07.
Password Forgotten
Enter 9999 and press ENTER.
Enter 9999 again within 10
seconds and press ENTER.
Then all parameters will reset
to factory settings.
P8.06
Keypad will be locked after 4 wrong
attempted passwords. To re-activate
the keypad, please reboot the drive
and input the correct password.
Password Incorrect
P8.06
4 chances of password input:
Incorrect password 1: displays “01”
Incorrect password 2: displays “02”
Incorrect password 3: displays “03”
Incorrect password 4: “Pcode” (blinking)
3
3DVVZR UG6HW
3
3DVVZR UG,QSXW
3
6KXWGRZQWKHGULYH
DQGUHDSSO\SRZHU
5HDSSO\SRZH U
7KHS DVVZRUGLVVWLOOYDOLG
Decode Flow Char t
<HV
1R

Table of Contents

Other manuals for Automation Direct DURApulse GS4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Automation Direct DURApulse GS4 and is the answer not in the manual?

Automation Direct DURApulse GS4 Specifications

General IconGeneral
BrandAutomation Direct
ModelDURApulse GS4
CategoryController
LanguageEnglish

Related product manuals