Chapter 4: AC Drive Parameters
Page 4–191
DURApulse GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
Type Hex Addr Dec Addr
P9.94 Ethernet Communication Card Time Out Detection
♦ R/W 095E 42399
Range/Units (Format: 16-bit binary) Default
0: Disable
1: Enable
0
This parameter Enables or Disables time-out detection for Ethernet communications.
Related Parameters: P9.93, P9.95
Type Hex Addr Dec Addr
P9.95 Ethernet Communication Card Time Out Duration
♦ R/W 095F 42400
Range/Units (Format: 16-bit unsigned) Default
0�1 to 100�0 seconds
0�5
When parameter P9.94 is set to 1, the communications Time Out Detection is Enabled. If a delay in
communications for more than the Time Out Duration (P9.95) is detected, the action selected by
the Transmission Fault Treatment (P9.93) will be used.
Related Parameters: P9.93, P9.94