Page 4–194
DURApulse GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
Chapter 4: AC Drive Parameters
PuMP ParaMeters details
Parameters P10.00~P10.08 provide five different methods for cyclical control of pumps, consisting
of the three previously described control modes plus two combined modes.
Type Hex Addr Dec Addr
P10.00 Circulative Control
R/W 0A00 42561
Range/Units (Format: 16-bit binary) Default
0: no function
1: Time Circulation
2: Quantity Cycle
3: Quantity Control
4: Time Circulation + Quantity Cycle
5: Time Circulation + Quantity Control
0
Parameter P10.00 selects one of five Circulative Control modes. The table below associates the
P10 parameters with each of the five modes. Only in mode 4, Quantity Cycle + Time Circulation,
are all nine parameters used.
Descriptions and timing charts for of each of these five circulative control modes can be found in
the subsequent pages of this section following the P10 parameter descriptions.
P10.00~P10.08 – Circulative Control Modes – Related Parameters
Param# Description No Fn. T.Circ. Q.Cycle Q.Cont. Q.Cy.+T.C. Q.Co.+T.C.
P10�00 Circulative Control 0 1 2 3 4 5
P10�01 Number of Connected Motors ~
P10�02 Desired Run Time of Each Motor ~ ~ ~
P10�03
Motor Switch Delay Time During Increasing
Demand
~
P10�04
Motor Switch Delay Time During Decreasing
Demand
~ ~
P10�05
Motor Switch Delay Time During Fix Amount
Circulation
~ ~
P10�06
Motor Switch Frequency During Fix Amount
Circulation
~ ~
P10�07 Circulative Control Malfunction Action ~ ~ ~ ~
P10�08 AUX Motor Stop Frequency ~ ~
Disable Motor Outputs
GS4 drive Multi-Function Inputs can be configured to disable all motor outputs, or individual
motor outputs. The settings are:
Multi-Function Input Settings to Disable Motor Outputs
P3.03~P3.16 =
42 43 44 45 46 47 48 49 50
Disable Motor Output
all 1 2 3 4 5 6 7 8
When a motor output is disabled, the motor will be de-energized and will coast stop.