Page 4–210
DURApulse GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
Chapter 4: AC Drive Parameters
Type Hex Addr Dec Addr
P11.22 Output Current at Fault
Read 0B16 42839
Range/Units (Format: 16-bit unsigned) Default
0�00~655�35A
0
P11.22 shows the Output Current at the time of last drive fault. If another fault occurs, the
previous record will be overwritten.
Type Hex Addr Dec Addr
P11.23 IGBT Temperature at Fault
Read 0B17 42840
Range/Units (Format: 16-bit signed) Default
-3276�7 to 3276�7 °C
0
P11.23 shows the IGBT Temperature at the time of last drive fault. If another fault occurs, the
previous record will be overwritten.
Type Hex Addr Dec Addr
P11.24 HeatSink Temperature at Fault
Read 0B18 42841
Range/Units (Format: 16-bit signed) Default
-3276�7 to 3276�7 °C
0
P11.24 shows the HeatSink Temperature at the time of last drive fault. If another fault occurs, the
previous record will be overwritten.
Type Hex Addr Dec Addr
P11.25 RPM of Motor at Fault
Read 0B19 42842
Range/Units (Format: 16-bit signed) Default
-32767 to 32767 rpm
0
P11.25 shows the Motor Speed in rpm at the time of last drive fault. If another fault occurs, the
previous record will be overwritten.
Type Hex Addr Dec Addr
P11.26 Digital Input Status at Fault
Read 0B1A 42843
Range/Units (Format: 16-bit unsigned) Default
0~65535
0
P11.26 captures the value of P3.46 Digital Input Status at the instant of last drive fault. If another
fault occurs, the previous record will be overwritten.