Chapter 4: AC Drive Parameters
Page 4–5
DURApulse GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
GS4 Parameters Summary – V/Hz Parameters (P2.xx) – (continued)
Parameter Range
Run
Read/
Write
Modbus
Address
Settings
Hex Dec Default User
P2.15
Motor 2 Middle Output Voltage 2
230V: 0�0~240�0V
460V: 0�0~480�0V
♦R/W 020F 40528
G S4-
21P0~27P5: 15�0V
2010+: 14�0V
G S4-
41P0~47P5: 30�0V
4010+: 28�0V
P2.16
Motor 2 Minimum Output Frequency 0�00~599�99 Hz R/W 0210 40529 1�50
P2.17
Motor 2 Minimum Output Voltage
23 0V: 0�0~240�0V
46 0V: 0�0~480�0V
♦R/W 0211 40530
G S4-
21P0~27P5: 9�0V
2010+: 7�0V
G S4-
41P0~47P5: 18�0V
4010+: 14�0V
P2.18
Zero Speed Select
0: Standby
1: Zero Hold
2: Fmin (Min Hz Output)
R/W 0212 40531 0
P2.19
Start Frequency 0�00~600�00 Hz R/W 0213 40532 0�50
P2.20
Y-D Switching Frequency 0�00~600�00 Hz ♦R/W 0214 40533 60�00
P2.21
Y-D Switching Enable
0: Disable
1: Enable
R/W 0215 40534 0
P2.22
Delay Time for Y-D Switching 0�00~600�00 Hz ♦R/W 0216 40535 0�200
P2.23
Automatic Energy-Saving Operation
0: Disable
1: Enable
♦R/W 0217 40536 0
P2.24
Power Saving Gain 10~1000% ♦R/W 0218 40537 100
P2.25
Slip Compensation Filter 0�001~10�000 sec ♦R/W 0219 40538 0�100
P2.26
Slip Deviation Level 0�0~100�0 ♦R/W 021A 40539 0�0
P2.27
Slip Deviation Detection time 0�0~10�0 ♦R/W 021B 40540 1�0
P2.28
Slip Deviation Treatment
0: Warn and continue OP
1: Warn and Ramp to Stop
2: Warn and Coast to stop
3: No Warn
♦R/W 021C 40541 0
P2.29
Hunting Gain 0~10000 ♦R/W 021D 40542 1000