EasyManua.ls Logo

Burkert 8792 - SPLTRNG - Signal Split Range

Burkert 8792
246 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
110
Auxiliary functions
26.2.5. SPLTRNG – Signal split range
Min. and max. values of the input signal as % for which the valve runs through the entire stroke range.
Factory setting: Min = 0 %; Max = 100 %
Type 8793: The SPLTRNG auxiliary function can only be selected when operating as a positioner.
P.CONTROL = not activated.
Use this auxiliary function to limit the position set-point value range of the Type 8792/8793 by specifying a minimum
and a maximum value.
As a result, it is possible to divide a utilised standard signal range (4 – 20 mA; 0 – 20 mA; 0 10 V or 0 – 5 V) into
several devices (without or with overlapping).
This allows several valves to be used alternately or in the case of overlapping set-point value ranges simultane-
ously as actuating element.
EXIT
*
OK
Enter
value
Enter
value
SPLTRNG
Min 0 %
Max 100 %
Input the minimum value of the
input signal as %.
Adjustment range: 0 – 75 %
Input the maximum value of the
input signal as %.
Adjustment range: 25 – 100 %
ENTER INPUT
INPUT
* If the submenu is left by pressing the
ESC
key, the value remains unchanged.
Figure 61: Operating structure SPLTRNG
The changed data is saved in the memory (EEPROM) only when there is a switch to the process level,
by leaving the main menu (MAIN) using the left selection key
EXIT
. During the save process, the save
symbol is indicated
on the display.
Splitting a standard signal range into two set-point value ranges
4
6 8 10
12 14 16 18 20
100
Valve stroke [%] (POS)
Set-point value [mA]
(INP)
Set-point value range
Positioner 1
Set-point value range
Positioner 2
Figure 62: Graph - SPLTRNG
english
Type 8792, 8793

Table of Contents

Other manuals for Burkert 8792

Related product manuals