EasyManua.ls Logo

Burkert 8792 - Static Output Assemblies

Burkert 8792
246 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
217
DeviceNet
33.4.2. Static output assemblies
Name Address of data attribute of the assemblies
for read access. Class, Instance, Attribute
Format of the
data attribute
INP (factory setting) 4, 21, 3 Byte 0: INP low
Byte 1: INP high
SP
4, 22, 3 Byte 0: SP low
Byte 1: SP high
Table 123: Static output assemblies; DeviceNet
The addresses indicated in “Table 123” can be used as path data for the attribute Consumed Connection Path of
an I/O connection.
The attributes described in more detail in the following “Table 124” can be transferred as output process data via
this I/O connection.
Nevertheless, by using this address data, the attributes combined in the assemblies can also be accessed acycli-
cally via Explicit Messages.
Name Description of the output data attributes Attribute Address Class,
Instance, Attribute; Data
type, Length
INP
Nominal position
Set-point value of positioner as ‰. Value range 0 – 1000.
In “pure” positioner mode (P.CONTROL inactive) the transfer of
the nominal position INPUT is required; as a process controller
(PCONTROL active) the transfer of INPUT is not possible.
If the value is too small or too large, the last valid value is used and
is indicated in ERR with HEX 14.
111, 1, 58;
UINT, 2 byte
SP *
Process set-point value
Set-point value of process controller in physical unit (as set in the
menu P.CONTROL SETUP SP-INPUT or SP-SCALE), max.
value range -999 – 9999, depending on internal scaling.
If the value is too small or too large, the last valid value is used and
is indicated in ERR with HEX 15.
120, 1, 2;
INT, 2 byte
* relevant only for Type 8793 and when process controller activated.
Table 124: Output data attributes; DeviceNet
english
Type 8792, 8793

Table of Contents

Other manuals for Burkert 8792

Related product manuals