Falcon Parameters Appendix A
A-6
Annunciation Configuration Annunciator 4 location OEM D:Interlock circuit 345
Annunciation Configuration Annunciator4 short name OEM A4 346
Annunciation Configuration Annunciator 4 long name OEM HIGH AIR PRESSURE 348
Annunciation Configuration Annunciator 5 location OEM D:Interlock circuit 358
Annunciation Configuration Annunciator5 short name OEM A5 359
Annunciation Configuration Annunciator 5 long name OEM HIGH GAS PRESSURE 361
Annunciation Configuration Annunciator 6 location OEM D:Interlock circuit 371
Annunciation Configuration Annunciator6 short name OEM A6 372
Annunciation Configuration Annunciator 6 long name OEM LOW GAS PRESSURE 374
Annunciation Configuration Annunciator 7 location Service A:No annunciation for this terminal 384
Annunciation Configuration Annunciator7 short name Service HFS 385
Annunciation Configuration Annunciator 7 long name Service HIGH FIRE SWITCH 387
Annunciation Configuration Annunciator 8 location Service A:No annunciation for this terminal 397
Annunciation Configuration Annunciator8 short name Service LFS 398
Annunciation Configuration Annunciator 8 long name Service LOW FIRE SWITCH 400
Annunciation Configuration PII short name OEM PII 410
Annunciation Configuration PII long name OEM Pre-Ignition ILK 412
Annunciation Configuration LCI short name OEM LCI 422
Annunciation Configuration LCI long name OEM Limit Circuit Input 424
Annunciation Configuration ILK short name OEM ILK 434
Annunciation Configuration ILK long name OEM Lockout Interlocks 436
Interlocks Purge rate proving Service B:Prove via HFS terminal 229
Interlocks Lightoff rate proving Service B:Prove via LFS terminal 230
Interlocks Interlock open response Read
Only
A:Lockout 238
Interlocks Interrupted air switch enable OEM { xBCx
}
C:Enable IAS during purge &&
ignition
246
Interlocks LCI enable Read
Only
Enabled 248
Interlocks PII enable OEM Enabled 249
Interlocks ILK bounce detection enable Service Enabled 253
Safetey Timing Prepurge rate Service 60 65% 100% % 196
Safetey Timing Postpurge rate Service 40 50% % 198
Safetey Timing Standby rate Service 0 35% 100% % 207
Safetey Timing Prepurge time Service 0m
30s
0m 30s mmm ss 231
Safetey Timing Run stabilization time Service 0m 10s mmm ss 235
Safetey Timing Postpurge time Service 0m
15s
0m 15s mmm ss 236
Ignition Configuration Lightoff rate Service 0 25% 50% % 197
Ignition Configuration Ignition source Read
Only
B:External ignition 224
Ignition Configuration Igniter on during Read
Only
B:On in first half of PFEP 226
Ignition Configuration Pilot type Read
Only
A:Interrupted (off during Run) 227
Ignition Configuration Preignition time Service 0m 0s mmm ss 232
Ignition Configuration PFEP Read
Only
C:10 seconds 233
Ignition Configuration MFEP OEM B:5 seconds 234
Ignition Configuration Flame threshold OEM .5 .8 5 10ths (V
or uA)
250
Flame Failure Ignite failure response Service A:Lockout 239
Flame Failure Ignite failure retries Service D:Retry 1 time 240
Flame Failure Ignite failure delay Service 0m 30s 60m
0s
mmm ss 241
Flame Failure Run flame failure response Read
Only
A:Lockout 243
System Configuration Temperature units Service A:Fahrenheit 178
System Configuration Antishort cycle time Service 0m 0s mmm ss 179
System Configuration Power up with lockout OEM Enabled 181
System Configuration Burner switch User No/False/Off 203
System Configuration BLR HSI function Read
Only
A:Blower motor 225
System Configuration Flame sensor type Service D:UV power tube, ignore ignitor UV 228
Table A-1 CFLC Falcon Parameters (Continued)
Parameter Group Parameter Name Access* Min
range
Default Setting Max.
Range
Parameter
Units
Modbus
Register (dec)