Falcon Alert, Hold, Lockout Codes Appendix D
D-8
239 Invalid S2 (J8-6) connector type setting Lockout
240 Invalid S5 (J8-11) connector type setting Lockout
241 Exchanger sensor not allowed with stack connector setting Lockout
242 Invalid DHW auto detect configuration Lockout
243 Invalid UV with spark interference not compatible with Ignitor on throughout PFEP Lockout
244 Internal fault: Safety relay test invalid state Lockout
245 Invalid Outlet connector type setting for T-rise Lockout
246 4-20mA cannot be used for both modulation and setpoint control Lockout
247 Invalid ILK bounce detection enable Lockout
248 Invalid forced recycle interval Lockout
249 STAT cannot be demand source when Remote Stat is enabled Lockout
250 Invalid Fan speed error response Lockout
251-255 RESERVED
Table D-1 Falcon Holds and Lockouts (Continued)