Falcon Alert, Hold, Lockout Codes Appendix D
D-14
210 Lead Lag slave was discovered
211 Incompatible Lead Lag slave was discovered
212 No base load rate was set for Lead Lag slave
213 Lead Lag slave unable to fire before demand to fire delay expired
214 Adding Lead Lag slave aborted due to add requirement change
215 No Lead Lag slaves available to service demand
216 No Lead Lag active service was set due to demand priority conflicts
217 No Lead Lag add stage method was specified
218 No Lead Lag drop stage method was specified
219 Using backup lead lag header sensor due to sensor failure
220 Lead Lag frost protection rate was invalid
221 Lead Lag drop stage method setting was invalid
222 CH frost protection temperature was invalid
223 CH frost protection inlet temperature was invalid
224 DHW frost protection temperature was invalid
225-226 RESERVED
227 DHW priority override time was not derated due to invalid outdoor temperature
228 Warm weather shutdown was not checked due to invalid outdoor temperature
229 Lead Lag slave communication timeout
230 RESERVED
231 Lead Lag CH setpoint was invalid
232 Lead Lag CH time of day setpoint was invalid
233 Lead Lag outdoor temperature was invalid
234 Lead Lag ODR time of day setpoint was invalid
235 Lead Lag ODR time of day setpoint exceeded normal setpoint
236 Lead Lag ODR max outdoor temperature was invalid
237 Lead Lag ODR min outdoor temperature was invalid
238 Lead Lag ODR low water temperature was invalid
239 Lead Lag ODR outdoor temperature range was too small (minimum 12 C / 22 F)
240 Lead Lag ODR water temperature range was too small (minimum 12 C / 22 F)
241 Lead Lag DHW setpoint was invalid
242 Lead Lag Mix setpoint was invalid
243 Lead Lag CH demand switch was invalid
244 Lead Lag ODR min water temperature was invalid
245 RESERVED
246 CH setpoint was invalid
247 CH time of day setpoint was invalid
248 CH outdoor temperature was invalid
249 CH ODR time of day setpoint was invalid
250 CH ODR time of day setpoint exceeds normal setpoint
251 CH max outdoor setpoint was invalid
252 CH min outdoor setpoint was invalid
Table D-2 Falcon Alerts (Continued)