Speed Select [ PRIMARY, SECONDARY, BIN.INPUT ]
(AUX, EME, CMB only)
Activates/deactivates the logical binary output Secondary Sw see Logical BO in table below. This output
can be configured to J1939 output to switch ECU Nominal RPM.
BIN.INPUT: PRIMARY / SECONDARY Nominal RPM is selected via Binary input BI Secondr RPM see
Logical BI in table below.
Setpoint name
Setpoint setting
Logical BO
Logical BI
Governor Mode
ISOCHR / DROOP /
BIN.INPUT
Droop Sw
BI Droop
Speed Select
PRIMARY /
SECONDARY /
BIN.INPUT
Second RPM Sw
BI Secondr RPM
Idle/Nominal
IDLE / NOMINAL /
BIN.INPUT
Nominal Sw
BI Idle
Hint:
Basic setting: Nominal RPM must correspond to ECU Nominal RPM for 100% Throttle position in PRP and
50% in AUX.
ECU Diag [ ENABLED, DISABLED, EXTERNAL ]
Alarm list indication ECU Diag disabled is indicated when ECU diagnostics is disabled. The ECU Diagnostic
is controlled by ECU DiagBlck binary input in case of setting to EXTERNAL.
RunHourSource [ INTERNAL, ECU ]
Internal ID-DCU MARINE running hours statistical value is used
ECU running hours value given by ECU is used
In case there is not configured ECU in ID-DCU MARINE then Internal running hours value is used despite
RunHoursSource setting.
ControllerAddr [ - ]
Controller identification number. Each engine in the group has to have its own unique number. Default value
is 1.
Range: 1 8
Hint:
The InteliDrive ControllerAddr must correspond to InteliMonitor or DriveConfig communication setup setting
when opening Direct or Modem connection.
RS232 Mode [ STANDARD, MODBUS ]
Communication protocol selection.
STANDARD: InteliDrive (DriveConfig, InteliMonitor, Remote panel) communication protocol.
MODBUS: Modbus RTU protocol.
Hint:
Detail Modbus protocol description include some examples see in InteliGen Communication guide.
CAN Bus Mode [ kBd ]
Inter-controller, I-RD-CAN-ID-DCU-MARINE, IG-IB, IB-NT CAN2 bus speed selection.
250: High speed CAN (250 kBd) applicable up to 8 controllers, CAN bus limited up to 200 meters.
50: Low speed CAN (50 kBd) applicable up to 7 controllers, CAN bus limited up to 900 meters.
Hint:
Low speed CAN2 bus use for long distance connection only. Set all connected controllers to the same
speed. Other units I-RD-CAN-ID-DCU-MARINE, IG-IB, IB-NT detect CAN bus speed automatically.