ID-DCU-MARINE-2.2.2, ©ComAp – June 2015 - 106 -
ID-DCU-MARINE-2.2.2.pdf
StartPCoolant [ Bar ] (PRP only)
Coolant pressure limit = one of the engine running indications.
To activate this function any Analog input must be configured to Analog logical input Coolant press.
Step: 0,1 Bar
Range: 0 – 10,0 Bar
Hint:
Step, Range and dimension depend on corresponding Analog input sensor characteristic.
Prestart Time [ s ]
Time the binary output Prestart is active prior to engine start (Start request sending to ECU). Set to zero if
you want to start immediately after Start button is pressed (the Prestart output stays opened). RPM must be
zero during Prestart time otherwise the Starting procedure is not activated.
Step: 1s
Range: 0 – 600 s
MaxCrank Time [ s ]
Amount of time the controller will crank the engine in an attempt to start.
Step: 1s
Range: 1 – 3600 s
Hint:
The ID-DCU MARINE stops cranking after three seconds when detected RPM = 0.
CrankFail Pause [ s ]
Pause between crank attempts.
Step: 1 s
Range: 1 – 200 s