ID-DCU-MARINE-2.2.2, ©ComAp June 2015 - 107 -
ID-DCU-MARINE-2.2.2.pdf
Crank Attempts [ - ]
Max number of crank attempts.
Step: 1
Range: 1 - 200
Hint:
There is one start attempt only in the case of panel Start button or Binary input Remote Start activation.
Number of Cranking attempts based on this setpoint is accepted when start is activated by Binary input
RemRepStart (PRP) or Blackout Start (AUX, EME and HRB) only. The setpoint is not followed if
Sd Override is active, crank attempts number is then unlimited in case of Blackout Start.
Idle RPM [ - ] (PRP only)
Default Idle speed (should be same as adjusted in ECU).
Hint:
100% of Engine Values: Requested Speed is the range between Engine params: Idle RPM and Basic
setting: Nominal RPM.
Idle Offset [ % ] (PRP only)
Offset of Idle speed in % of RPM difference between nominal and idle setpoints (Nominal RPM Idle RPM)
see chapter ID-DCU MARINE function Requested RPM, Overload protection.
Step: 0,1 %
Range: 0,0 100,0 %
Idle Time [ s ]
Idle time delay starts when RPM exceeds Starting RPM.
During the Idle time the Binary output Idle/Nominal is opened and after then it is closed. Binary output
Idle/Nominal opens during Cooling period (Cooling Time) again.
Step: 1 s
Range: 1 600 s
PrelubrTime [ s ]
This is the time the binary output Prelubrication is active. The controller will activate binary output
Prelubrication for this amount of time, then pause for PrelubrPause, then activate again. This will continue
the entire time the engine is not running. Function is not active in controller OFF mode.
Step: 1s
Range: 0 600 s
PrelubrPause [ min ]
Time interval between prelubrication cycles see PrelubrTime.
Step: 1 minute
Range: 1 4000 min
Hint:
To use Prelubrication, configure Binary output Prelubrication at first.
Prelubrication is disabled in controller OFF mode or when PrelubrTime is set to zero.
When engine is running Prelubrication binary output is opened.
Prelubrication starts PrelubrPause after engine stops. Prelubrication starts immediately when
- controller power supply turns on
- mode changes from OFF to another
- Emergency Stop is released.
Stop Time [ s ]
Under normal conditions the engine must certainly stop within this period. The period starts by issuing stop
command.
Step: 1s
Range: 0 600 s

Table of Contents

Other manuals for ComAp InteliDrive DCU Marine

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliDrive DCU Marine and is the answer not in the manual?

ComAp InteliDrive DCU Marine Specifications

General IconGeneral
BrandComAp
ModelInteliDrive DCU Marine
CategoryController
LanguageEnglish

Related product manuals