ID-DCU-MARINE-2.2.2, ©ComAp – June 2015 - 112 -
ID-DCU-MARINE-2.2.2.pdf
Batt > V [ V ]
Warning level for battery over voltage.
Step: 0,1V
Range: Batt <V – 40 V
Batt < V [ V ]
Warning level for low battery voltage.
Step: 0,1V
Range: 8 – Batt >V
Batt Volt Del [ s ]
Delay for battery voltage alarms.
Step: 1s
Range: 0 – 600 s
OverloadSpLim [ % ] (PRP only)
Engine overload protection limit. See Requested RPM, Overload protection in chapter ID-DCU MARINE
functions.
Step: 0,1 %
Range: 0 – 100 %
Overload Del [ s ] (PRP only)
Delay for Overload RPM protection limit.
Step: 1s
Range: 0 – 600 s
Service Time [ h ]
Running hours down counter is decremented when engine is running. Service alarm is indicated in Alarm list
and History record activated when counter reach zero. Service time setpoint is actual counter value.
Step: 1 h
Range: 0 – 65535 h
Hint:
Once the service time has elapsed the Service time will have to be adjusted to non-zero value to clear the
alarm and begin a new countdown.