ID-DCU-MARINE-2.2.2, ©ComAp June 2015 - 111 -
ID-DCU-MARINE-2.2.2.pdf
BinInp Delay 3 [ s ]
Binary input protection is activated when input is closed for longer time than BinInp delay 3. To use this filter
Binary input must be configured in DriveConfig for Property Delay = BinInp delay 3.
Step: 1s
Range: 0 60 s
Hint:
BinInp delay x is active only for Binary inputs configured as protection and it is related to protection only.
BinInp delay x does not have any influence on an optional logical function of an input.
DriveConfig: I/O, Property, Protection active = Closed
BINARY INPUT
BinInp delay
physical
BINARY INPUT
Internal value
no change
BINARY INPUT
BinInp delay
physical
BINARY INPUT
closed
Internal value
BINARY INPUT
BinInp delay
physical
BINARY INPUT
Internal value
DriveConfig: I/O, Property, Protection active = Opened
opened
ForceBlock Del [ s ]
Delay for Force block protection activation after Binary input Force Block is opened. Protection deactivation
is without delay. Protection is activated/deactivated independent on engine running or not running state.
Step: 1s
Range: 0 60 s
BINARY INPUT
ForceBlock del
FORCE BLOCK
Protection
closed
BINARY INPUT
Prot, block type = Force block
closed
active
active
inactive
Overspeed [%]
Threshold for engine overspeed protection.
Step: 1% of Nominal RPM
Range: 0 200%
Hint:
Underspeed alarm is activated when engine is running and actual RPM is below 30 RPM.
MinLoadSpeed [ % ]
Binary output Ready to load is closed if RPM > MinLoadSpeed and engine is in Running state. Use this
output to enable/disable connecting of engine load. MinLoadSpeed is a condition to close BO Close Load
when panel I/0 button is closed.
Step: 1 RPM
Range: 0 Nominal RPM

Table of Contents