Fuel ConsAct
There are two cumulative Statistics registers - values TripCons and DayCons. Those statistic values
increment value based on sampling of Logical Analog Input Fuel ConsAct. LAI can be sourced from ECU
Fuel Rate [ l/h ] or separate Actual Fuel consumption sensor connected to physical Analog input.
Both statistics values is possible to modify in InteliMonitor – Set Statistics command or clear by Logical
Binary Inputs ClearDayCons or ClearTripCons.
MainScrAna1, MainScrAna2
Logical Analog Inputs MainScrAna1 or MainScrAna2 enables to redirect any Analog input value on the ID-
DCU Marine main screen on “OilPress” and “CoolTemp” position.
Hint:
Default names “OilPress” and “CoolTemp” do not change when the Logical Analog Inputs MainScrAna1 or
MainScrAna2 are connected to other source values and has to be changed by translator.
Configuration example:
1. Default configuration:
ID / AIN1_Function = Oil Press; MainScrAna1
ID / AIN2_Function = Coolant Temp; MainScrAna2
2. To display e.g. value from AIN3 “AirTemp1” instead “OilPress” (the first position) and AIN4
“AirTemp2” instead “CoolTemp” value:
a. Select AIN3 Property Function = MainScrAna1
b. Select AIN4 Property Function = MainScrAna2
c. Create new language (in DriveConfig Languages) based on English
d. Rename (in DriveConfig Translator / Analog values) text “OilPress” to “AirTemp1” in the
newly created language
e. Rename (in DriveConfig Translator / Analog values) text “CoolTemp” (no space between) to
“AirTemp2” in the newly created language
f. Switch the ID-DCU Marine controller into newly created and modificated language (Enter +
Page, Page, select the new language by up/down arrows, Enter)
Hint:
Translate text “OilPress” and “CoolTemp” - no space between words because of similar texts (e.g. Coolant
Temp, etc. are located on other screens).