Memory1, Memory2
There are two Statistics registers Memo1 and Memo2. Those statistic values are based on Logical Analog
Input Memory1 or Memory2 value in the time of Logical Binary input Memo1 Trigger or Memo2 Trigger
rising edge. Both statistics values is possible to modify in InteliMonitor – Set Statistics command.
Cold Temp 1 .. Cold Temp 4
If there is an additional terminal board between a thermocouple sensor and the IS-AIN8 (TC) module and
there is a significant temperature difference between this terminal board and the module, it is necessary to
measure the temperature at this terminal board and use this temperature for the thermocouple compensation
instead of the internal temperature of the module.
Cold Temp 1 Logical Analog input is intended for measurement of this thermocouple compensation
temperature for the IS-AIN8 (TC) module with index #1, Cold Temp 2 corresponds to IS-AIN8 (TC) module
with index #2 etc.
Hint:
Thermocouples without internal compensation "Thermo(nc)..." must be used for this case.
Cyl Temp 1 … Cyl Temp 16
Analog inputs for engine Cylinder temperature measuring.