Create C300 Controller and CEE function blocks
To configure a C300 Controller block
38 Experion C300 Controller User's Guide R301.1
Honeywell 11/06
Step Action Result
5
Check the box if the controller will be one
of a redundant pair. If you check the
box, the Secondary Tag Name will
appear in the Redundancy Configuration
box.
C300 Controller is configured as either
nonredundant or redundant with a
Secondary C300 Controller block added
when the Primary controller FB
configuration form is closed.
6
The Alarming Enabled check box
contains a check (default).
To disable alarming for the parameters in
the Advanced Configuration box, clear
the Alarming Enabled check box.
7
Click on the Temperature High Alarm
(deg. C) field.
Enter a temperature at which an alarm is
generated for controller hardware
temperature. Press <Tab>.
Moves cursor to the CPU Free Low
Alarm (%) field.
8
Accept the default or key in desired
value.
Note: Do not set lower than the default
value of 20%.
9
Click Server History tab.
Calls up the Server History configuration
form.