Receiving the messages:
The System will send the specified messages to the nominated GSM Mobile phone
with a validity period of 168 hours (1 week). i.e. The message will be discarded by
the network if not received by the nominated Mobile phone within 168 hours.
(Note: Validity time was 5 minutes in GSM Modem firmware V1.04 or earlier
shipped in June/July 2000. The firmware in these earlier units can be upgraded to
V1.05 or later to provide 168 hours Validity time)
When received by the Mobile Phone, a message can then be read on the Mobile
phone display.
Message text sent via the GSM Modem is almost identical to the text shown in the
“Review” menu. (<MENU>, 1, 1. See page 28)
e.g.
Jun12 22:43:50.1 Xmit Alarm on Smoke Detector (B02:Z11) in Office 01AA
Jun13 07:28:20.7 Xmit Office Off by Tony Li 01AB
Jun15 15:54:31.6 Xmit Alarm on Temp Sensor (M05:Z04) in Coolstore 01AC
SMS Alarm ID:
Note the four character ID string that is added to the end of the Review text.
This is used to identify the SMS Alarm Text message.
1st two characters: Which Mobile Phone in the list the message has been sent to.
-Provided for the Mobile Phone Users information only.
2nd two characters: The SMS Alarm Text Message ID.
-Provided for SMS Alarm Text Acknowledgement if required.
See “Acknowledging the Messages” on the following page.
e.g. 01AA = 1st phone number tried for Alarm ID “AA”.
03AF = 3rd phone number tried for Alarm ID “AF”