Chapter 5 ā Parameter list
5-16
CODE
Comm.
Addr
Description
LCD Keypad
Display
Setting Range
Factory
Default
Adj.
During
Run
Page
APP-27 971B
2nd Electronic Thermal
Level for 1 minute
2nd ETH 1min FU2-28 to 200 [%] 130[%] O
APP-28 971C
2nd Electronic Thermal
Level for continuous
2nd ETH cont
50 to FU2-27
(Max 150%)
120[%] O
APP-29
971D
2nd Rated Motor Current 2nd R-Curr 1 to 200 [A] 3.6[A] X
6-62
APP-40
(29)
9728
Number of Auxiliary Motor
Run Display
Aux Mot Run * * * 6-63
APP-41
9729
Aux. Motor Start Selection Starting Aux 1 to 4 1 O 6-64
APP-42
972A
Operation Time Display on
Auto Change
Auto Op Time * * * 6-64
APP-43
972B
The Number of Aux Motor Nbr Aux`s 0 to 7 4 O 6-64
APP-44
972C
Start Frequency of Aux.
Motor 1
Start freq 1 49.99 [Hz] O
APP-45
972D
Start Frequency of Aux.
Motor 2
Start freq 2 49.99 [Hz] O
APP-46
972E
Start Frequency of Aux.
Motor 3
Start freq 3 49.99 [Hz] O
APP-47
972F
Start Frequency of Aux.
Motor 4
Start freq 4 49.99 [Hz] O
APP-48
9730
Start Frequency of Aux.
Motor 5
Start freq 5 49.99 [Hz] O
APP-49
9731
Start Frequency of Aux.
Motor 6
Start freq 6 49.99 [Hz] O
APP-50
9732
Start Frequency of Aux.
Motor 7
Start freq 7
0 to FU1-30
49.99 [Hz] O
6-64
APP-51
9733
Stop Frequency of Aux.
Motor 1
Stop freq 1 20.00 [Hz] O
APP-52
9734
Stop Frequency of Aux.
Motor 2
Stop freq 2 20.00 [Hz] O
APP-53
9735
Stop Frequency of Aux.
Motor 3
Stop freq 3 20.00 [Hz] O
APP-54
9736
Stop Frequency of Aux.
Motor 4
Stop freq 4 20.00 [Hz] O
APP-55
9737
Stop Frequency of Aux.
Motor 5
Stop freq 5 15.00 [Hz] O
APP-56
9738
Stop Frequency of Aux.
Motor 6
Stop freq 6 15.00 [Hz] O
APP-57
9739
Stop Frequency of Aux.
Motor 7
Stop freq 7
0 to FU1-30
15.00 [Hz] O
6-64
APP-58
973A
Delay Time before Operating
Aux Motor
Aux start DT 0.0 to 999.9 [sec] 5.0 [sec] O 6-65
APP-59
973B
Delay Time before Stopping
Aux Motor
Aux stop DT 0.0 to 999.9 [sec] 5.0 [sec] O 6-65
APP-60
973C
Accel time when the number
of pump decreases
Pid AccTime 0 to 600.0 [sec] 2.0 [sec] O 6-65