Chapter 5 – Parameter list
5-18
CODE
Comm.
Addr
Description
LCD Keypad
Display
Setting Range
Factory
Default
Adj.
During
Run
Page
APP-95
975F
ExtPID Output Inverse ExtOut inverse
0 (No)
1 (Yes)
0 (No) X 6-70
APP-97
9761
ExtPID Loop Time Ext Loop Time 50 to 200 [msec] 100 [msec]
X 6-70
* The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set.
(24) MMC(Multi Motor Control) function is applied to the inverters only for 5.5~90kW(7.5~125HP).
(25) Only APP-03 ~ APP-17 displayed when APP-02 is set to [Yes]. (5.5 ~ 90kW / 7.5 ~ 125HP)
Only APP-03 ~ APP-17 and APP-63 ~ APP-65 displayed when APP-2 is set to [Yes]. (100 ~ 450kW / 150 ~
600HP)
(26) If APP-04 is no set, DRV-04 setting will be reference of processPID. And APP -05 setting will be ignored
(27) If APP-04 is set, APP-04 will appear. And APP -05 setting value will be reference of processPID, DRV-04
setting will be ignored.
(28) Only APP-20 ~ APP-29 displayed only when one of I/O-20 ~ I/O-27 is set to either ā€œ2nd Funcā€.
(29) Only APP-40 ~ APP-71 displayed when APP-01 is set to [MMC].
(30) Only APP-81 ~ APP-97 displayed when APP-80 is set to [Yes].