15 īīAppendix
Group 81: IRQ_4_5
81-4 Time overflow low-level
IRQ
Please contact the Technical Support team.
Group 82: Internal sequence control
82-0 Sequence control Internal sequence control: The process was
aborted.
For information only. No measures required.
82-1 Concurrent CO write
access
Please contact the Technical Support team.
Group 83: Technology modules
83-0 Technology module:
slot/combination
The technology module cannot be used in the
current slot or the combination of technology
modules is not permissible.
Contact the Technical Support team.
83-1 Technology module not
supported
Load the most recent firmware.
83-2 Technology module:
HW revision not
supported
Load the most recent firmware.
83-3 Service module: write
error
Please contact the Technical Support team.
83-4 MC2000 Watchdog Please contact the Technical Support team.
Group 84: Internal sequence control
84-0 Conditions for controller
enable not fulfilled
Enable the servo drive again after a short period
of time. If the error recurs, check the following:
- Are there still errors?
- Is the angle encoder ready?
- Has DIN4 been set?
- Is MOTID still being executed?
- Is there a running TFTP download?
- Has an energy-saving mode been activated via
PROFIenergy?
- Does the FSM 2.0 ā MOV (SBC) block the
enable signal?