EasyManuals Logo

Omron SYSDRIVE 3G3RV Series User Manual

Omron SYSDRIVE 3G3RV Series
446 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #200 background imageLoading...
Page #200 background image
5
-
74
*1.Set
T1-02
and
T1-04
when
2
is
set
for
T1-01.
Only
set
value
2
is
possible
for
V/f
control
or
V/f
control
with
PG.
*2.These
are
values
for
a
200-V
class
Inverter.
Val ues
for
a
400-V
class
Inverter
are
double.
*3.The
factory
setting
depends
on
the
Inverter
capacity.
(The
value
for
a
200-V
class
Inverter
for
0.4
kW
is
given.)
*4.The
setting
range
is
from
10%
to
200%
of
the
Inverter
rated
output
current.
(The
value
for
a
200-V
class
Inverter
for
0.4 kW
is
given.)
*5.The
upper
setting
limit
will
be
150.0
Hz
when
C6-01
is
set
to
0.
T1-04
Motor
rated
current
Set
the
rated
current
of
the
motor
in
amps.
0.32
to
6.40
*4
1.90
A
*3
No A A A 704H 4-13
Rated
Cur-
rent
T1-05
Motor
base
frequency
Set
the
base
frequency
of
the
motor
in
hertz.
0
to
400.0
*5
60.0
Hz
No No No A 705H 4-13
Rated
Fre-
quency
T1-06
Number
of
motor
poles
Set
the
number
of
motor
poles.
2
to
48
poles
4
poles No No No A 706H 4-13
Number
of
Poles
T1-07
Motor
base
speed
Set
the
base
speed
of
the
motor
in
r/min.
0
to
24000
1750
r/min
No No No A 707H 4-13
Rated
Speed
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Register Page
LCD
Display
V/f
V/f
with
PG
Open
Loop

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSDRIVE 3G3RV Series and is the answer not in the manual?

Omron SYSDRIVE 3G3RV Series Specifications

General IconGeneral
BrandOmron
ModelSYSDRIVE 3G3RV Series
CategoryInverter
LanguageEnglish

Related product manuals