5
-
74
*1.Set
T1-02
and
T1-04
when
2
is
set
for
T1-01.
Only
set
value
2
is
possible
for
V/f
control
or
V/f
control
with
PG.
*2.These
are
values
for
a
200-V
class
Inverter.
Val ues
for
a
400-V
class
Inverter
are
double.
*3.The
factory
setting
depends
on
the
Inverter
capacity.
(The
value
for
a
200-V
class
Inverter
for
0.4
kW
is
given.)
*4.The
setting
range
is
from
10%
to
200%
of
the
Inverter
rated
output
current.
(The
value
for
a
200-V
class
Inverter
for
0.4 kW
is
given.)
*5.The
upper
setting
limit
will
be
150.0
Hz
when
C6-01
is
set
to
0.
T1-04
Motor
rated
current
Set
the
rated
current
of
the
motor
in
amps.
0.32
to
6.40
*4
1.90
A
*3
No A A A 704H 4-13
Rated
Cur-
rent
T1-05
Motor
base
frequency
Set
the
base
frequency
of
the
motor
in
hertz.
0
to
400.0
*5
60.0
Hz
No No No A 705H 4-13
Rated
Fre-
quency
T1-06
Number
of
motor
poles
Set
the
number
of
motor
poles.
2
to
48
poles
4
poles No No No A 706H 4-13
Number
of
Poles
T1-07
Motor
base
speed
Set
the
base
speed
of
the
motor
in
r/min.
0
to
24000
1750
r/min
No No No A 707H 4-13
Rated
Speed
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Register Page
LCD
Display
V/f
V/f
with
PG
Open
Loop