nput Terminal Functions
6
-
7
1
nApplication
Precautions
• Jog
frequencies
using
FJOG
and
RJOG
commands
are
given
priority
over
other
frequency
references.
• When
both
FJOG
command
and
RJOG
commands
are
ON
for
500
ms
or
longer
at
the
same
time,
the
Inverter
stops
according
to
the
setting
in
b1-03
(stopping
method
selection).
K
KK
K Stopping
the
Inverter
by
Notifying
Programming
Device
Errors
to
the
Inverter
(External
Error
Function)
The
external
error
function
performs
the
error
contact
output,
and
stops
the
Inverter
operation
if
the
Inverter
peripheral
devices
break
down
or
an
error
occurs.
The
digital
operator
will
display
EFx
(External
error
[input
terminal
Sx]).
The
x
in
EFx
shows
the
terminal
number
of
the
terminal
that
input
the
external
error
signal.
For
example,
if
an
external
error
signal
is
input
to
terminal
S3,
EF3
will
be
displayed.
To
use
the
external
error
function,
set
one
of
the
values
20
to
2F
in
one
of
the
parameters
H1-01
to
H1-05
(multi-function
contact
input
terminal
S3
to
S7
function
selection).
Select
the
value
to
be
set
in
H1-01
to
H1-05
from
a
combination
of
any
of
the
following
three
conditions.
• Signal
input
level
from
peripheral
devices
• External
error
detection
method
• Operation
during
external
error
detection
The
following
table
shows
the
relationship
between
the
combinations
of
conditions
and
the
set
value
in
H1-
oo.
Note1.Set
the
input
level
to
detect
errors
using
either
signal
ON
or
signal
OFF.
(NO
contact:
External
error
when
ON;
NC
contact:
External
error
when
OFF).
2. Set
the
detection
method
to
detect
errors
using
either
constant
detection
or
detection
during
operation.
Constant
detection:
Detects
while
power
is
supplied
to
the
Inverter.
Detection
during
operation:
Detects
only
during
Inverter
operation.
Set
Value
Input
Level
(See
Note
1.)
Error
Detection
Method
(See
Note
2.)
Operation
During
Error
Detection
NO
Contact NC
Contact
Constant
Detection
Detection
During
Oper-
ation
Decelerate
to
Stop
(Error)
Coast
to
Stop
(Error)
Emergency
Stop
(Error)
Continue
Operation
(Warning)
20 Yes Yes Yes
21 Yes Yes Yes
22 Yes Yes Yes
23 Yes Yes Yes
24 Yes Yes Yes
25 Yes Yes Yes
26 Yes Yes Yes
27 Yes Yes Yes
28 Yes Yes Yes
29 Yes Yes Yes
2A Yes Yes Yes
2B Yes Yes Yes
2C Yes Yes Yes
2D Yes Yes Yes
2E Yes Yes Yes
2F Yes Yes Yes

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSDRIVE 3G3RV Series and is the answer not in the manual?

Omron SYSDRIVE 3G3RV Series Specifications

General IconGeneral
BrandOmron
ModelSYSDRIVE 3G3RV Series
CategoryInverter
LanguageEnglish

Related product manuals