iring Control Circuit Terminals for European Models
2
-
4
1
K
KK
K Control
Circuit
Terminal
Functions
The
functions
of
the
control
circuit
terminals
are
shown
in
Table
2.21.
Use
the
appropriate
terminals
for
the
correct
purposes.
Table 2.21 Control Circuit Terminals
Type No. Signal
Name Function Signal
Level
Se-
quence
input
signals
S1 Forward
run/stop
command Forward
run
when
ON;
stopped
when
OFF.
24
VDC,
8
mA
Photocoupler
isolation
S2 Reverse
run/stop
command Reverse
run
when
ON;
stopped
when
OFF.
S3
External
fault
input
*1
Fault
when
ON.
Functions
are
selected
by
set-
ting
H1-01
to
H1-05.
S4
Fault
reset
*
Reset
when
ON
S5
Multi-step
speed
reference
1
*1
(Master/auxiliary
switch)
Auxiliary
frequency
ref-
erence
when
ON.
S6
Multi-step
speed
reference
2
*1
Multi-step
setting
2
when
ON.
S7
Jog
frequency
reference
*1
Jog
frequency
when
ON.
SC Sequence
input
common
-
-
SP +24
V
power
for
S1
to
S7
SN -24
V
power
for
S1
to
S7
Analog
input
signals
+V 15
V
power
output 15
V
power
supply
for
analog
references
15
V
(Max.
current:
20
mA)
-V -15
V
power
output -15
V
power
supply
for
analog
references
-15
V
(Max.
current:
20
mA)
A1 Frequency
reference
0
to
+10
V/100%
(when
H3-01
=
0)
-10
to
+10
V/-100%
to
+100%
(when
H3-01
=
1)
*4
0
to
+10
V(20
kΩ)
A2 Multi-function
analog
input
4
to
20
mA/100%
0
to
+10
V/100%
Function
is
selected
by
set-
ting
H3-09.
4
to
20
mA(250Ω)
0
to
+10
V(20kΩ)
AC Analog
reference
common - -
E(G)
Shield
wire,
optional
ground
line
connection
point
--
Se-
quence
output
signals
M1
Running
signal
(1NO
contact)
Operating
when
ON.
Multi-function
contact
outputs
Dry
contacts
Contact
capacity:
1
A
max.
at
250
VA C
1
A
max.
at
30
VDC
M2
M3
Zero
speed
Zero
level
(b2-01)
or
below
when
ON
Multi-function
contact
outputs
Dry
contacts
Contact
capacity:
1
A
max.
at
250
VA C
1
A
max.
at
30
VDC
M4
M5
Frequency
agree
1
Within
±2
Hz
of
set
fre-
quency
when
ON
M6
MA
Fault
output
signal
(SPDT)
Fault
when
CLOSED
across
MA
and
MC
Fault
when
OPEN
across
MB
and
MC
Dry
contacts
Contact
capacity:
1
A
max.
at
250
VA C
1
A
max.
at
30
VDC
MB
MC

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSDRIVE 3G3RV Series and is the answer not in the manual?

Omron SYSDRIVE 3G3RV Series Specifications

General IconGeneral
BrandOmron
ModelSYSDRIVE 3G3RV Series
CategoryInverter
LanguageEnglish

Related product manuals