M
achine Protection
6
-
4
7
K
KK
K Motor
Overload
Protection
You
can
protect
the
motor
from
overload
using
the
Inverter's
built-in
electronic
thermal
overload
relay.
nRelated
Parameters
* 1. Factory
settings
depend
on
Inverter
capacity.
(The
values
shown
are
for
a
200
V
Class
Inverter
for
0.4
kW.)
*2.The
settings
range
is
10%
to
200%
of
the
Inverter
rated
output
current.
(The
values
shown
are
for
a
200
V
Class
Inverter
for
0.4
kW.)
Multi-Function
Digital
Outputs
(H2-01
to
H2-03)
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control
Methods
V/f
V/f
with
PG
Open
Loop
Vec-
tor
LCD
Display
E2-01
Motor
rated
current Set
the
motor
rated
current
in
amps.
This
set
value
becomes
the
base
value
for
motor
protection
and
torque
limit.
It
is
set
automatically
when
using
autotuning.
0.32
to
6.40
*2
1.90
A
*1
No Q Q Q
Motor
Rated
FLA
E4-01
Motor
2
rated
current Set
the
motor
rated
current
in
Amps.
This
set
value
becomes
the
base
value
for
motor
protection
and
torque
limit.
It
is
set
automatically
when
using
autotuning.
0.32
to
6.40
*2
1.90
A
*1
No A A A
Motor
Rated
FLA
L1-01
Motor
protection
selection
Set
to
enable
or
disable
the
motor
overload
protec-
tion
function
using
the
electronic
thermal
relay.
0:
Disabled
1:
General
motor
protection
2:
Inverter
special
motor
protection
3:
Vector
motor
protection
With
applications
where
the
power
supply
is
often
turned
ON
and
OFF,
there
is
a
risk
that
the
circuit
cannot
be
protected
even
if
this
parameter
has
been
set
to
1,
as
the
thermal
value
will
be
reset.
If
multiple
motors
are
connected
to
one
Inverter,
set
this
parameter
to
0,
and
install
a
thermal
relay
in
0
to
31 NoQQQ
MOL
Fault
Select
L1-02
Motor
protection
time
con-
stant
Set
the
electronic
thermal
detection
time
in
min-
utes.
Normally,
there
is
no
need
to
make
this
setting.
The
factory
setting
is
resistance
at
150%
for
1
min.
If
the
motor
overload
resistance
is
clear,
set
the
overload
resistance
protection
time
during
hot
start
to
suit
the
motor.
0.1
to
5.0
(0.1
to
20.0)
1.0
min
(8.0
min)
No A A A
MOL
Time
Const
Set
Value
Function
Control
Methods
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1F Motor
overload
(OL1,
including
OH3)
pre-alarm
(ON:
90%
or
more
of
the
detection
level) Yes Yes Yes

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSDRIVE 3G3RV Series and is the answer not in the manual?

Omron SYSDRIVE 3G3RV Series Specifications

General IconGeneral
BrandOmron
ModelSYSDRIVE 3G3RV Series
CategoryInverter
LanguageEnglish

Related product manuals