I
nverter Protection
6
-
6
1
K
KK
K Reducing
Inverter
Overheating
Pre-Alarm
Warning
Levels
The
Inverter
detects
the
temperature
of
the
cooling
fins
using
the
thermistor,
and
protects
the
Inverter
from
overheating.
Yo u
can
receive
Inverter
overheating
pre-alarms
in
units
of
10
°C.
The
following
overheating
pre-alarm
warnings
are
available:
Stopping
the
Inverter
as
error
protection,
and
continuing
operation,
with
the
alarm
OH
(Radiation
fins
overheating)
on
the
Digital
Operator
flashing.
nRelated
Parameters
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control
Methods
V/f
V/f
with
PG
Open
Loop
Vec-
tor
LCD
Display
L8-02
Overheat
pre-alarm
level
Sets
the
detection
temperature
for
the
Inverter
overheat
detection
pre-alarm
in
°C.
The
pre-alarm
detects
when
the
cooling
fin
tem-
perature
reaches
the
set
value.
50
to
130 95°CNoAAA
OH
Pre-Alarm
Lvl
L8-03
Operation
selection
after
overheat
pre-alarm
Sets
the
operation
for
when
the
Inverter
overheat
pre-alarm
goes
ON.
0:
Decelerate
to
stop
in
deceleration
time
C1-02.
1:
Coast
to
stop
2:
Fast
stop
in
fast-stop
time
C1-09.
3:
Continue
operation
(Monitor
display
only.)
A
fault
will
be
given
in
setting
0
to
2
and
a
minor
fault
will
be
given
in
setting
3.
0
to
33 NoAAA
OH
Pre-Alarm
Sel

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSDRIVE 3G3RV Series and is the answer not in the manual?

Omron SYSDRIVE 3G3RV Series Specifications

General IconGeneral
BrandOmron
ModelSYSDRIVE 3G3RV Series
CategoryInverter
LanguageEnglish

Related product manuals