W
iring Examples
1
0
-
7
10
Wiring Examples
This
section
provides
wiring
examples
to
connect
a
Braking
Unit
and
other
peripheral
devices
to
the
main
circuits,
examples
of
wiring
a
transformer
to
Inverter
I/O,
and
other
aspects
of
Inverter
wiring.
K
KK
K Using a Braking Resistor Unit
This
example
shows
wiring
for
a
Braking
Resistor
Unit.
3G3RV-A2004
to
3G3RV-A2185
(200-V
class
Inverters
of
0.4
to
18.5
kW)
3G3RV-4004
to
3G3RV-A4185
(400-V
class
Inverters
of
0.4
to
18.5
kW)
Fig 10.2
K
KK
K Using a Braking Unit and Braking Resistor Unit
This
example
shows
wiring
for
a
Braking
Unit
and
Braking
Resistor
Unit.
3G3RV-A2220,
3G3RV-A2300
(200-V
class
Inverters
of
22
kW,
30
kW)
Fig 10.3
* 1. A transformer is not required for 200-V class
* 2. Remove the short-circuit bar (normally connected) from + 1 and
+ 2 when connecting a DC Reactor (Optional).
* 3. Disable stall prevention during deceleration by setting L3-04 and
using a Braking Resistor Unit. The motor may not stop within the
deceleration time if this setting is not changed.
3-phase power
200 to 230 V 50/60 Hz
or 380 to 460 V
50/60 Hz
A sequence is required to turn
OFF the power supply for the ther-
mal overload relay trip contacts of
the Braking Resistor Unit.
Short-circuit bar
DC Reactor to
improve input
power factor
(Optional)
Braking Resistor overheating contacts
(Thermal overload relay trip contacts)
Braking Resistor Unit
*3
Inverter
Overload relay trip contact
of Braking Resistor Unit
Fault contacts
Motor
200-V class Inverters: Ground to
100 max., 400-V class Inverters:
Ground to 10 max.)
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
MC
3-phase power
200 to 230 V 50/60 Hz
A sequence is required to turn
OFF the power supply for the
thermal overload relay trip con-
tacts of the Braking Resistor
Unit.
DC Reactor to
improve input
power factor
(Optional)
Short-circuit bar
MCCB
Overload relay trip contact
of Braking Resistor Unit
Fault contacts
Braking Unit
(Optional)
Inverter
Motor
Level
detector
Braking Resistor Unit
*2
(Optional)
Braking Resistor overheating contacts
(Thermal overload relay trip contacts)
Ground to 100 max.
* 1. Remove the short-circuit bar (normally connected) from + 1 and + 2 when
connecting a DC Reactor (Optional).
* 2. Disable stall prevention during deceleration by setting L3-04 and using a
Braking Resistor Unit. The motor may not stop within the deceleration time
if this setting is not changed.
Forward Run/Stop
Reverse Run/Stop
Braking Unit
External fault
Forward run command (forward run when ON)
Reverse run command (reverse run when ON)
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
Forward Run/Stop

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSDRIVE 3G3RV Series and is the answer not in the manual?

Omron SYSDRIVE 3G3RV Series Specifications

General IconGeneral
BrandOmron
ModelSYSDRIVE 3G3RV Series
CategoryInverter
LanguageEnglish

Related product manuals