K Alarm
Detection
Alarms
are
detected
as
a
type
of
Inverter
protection
function
and
do
not
operate
the
fault
contact
output.
The
system
will
automatically
return
to
its
original
status
once
the
cause
of
the
alarm
has
been
removed.
The
Digital
Operator
display
flashes
and
the
alarm
is
output
from
the
multi-function
outputs
(H2-01
to
H2-
03).
When
an
alarm
occurs,
take
appropriate
countermeasures
according
to
the
table
below.
Table 7.2 Alarm Displays and Processing
Display Meaning Probable causes Corrective Actions
(blink-
ing)
External
Fault
Forward/Reverse Run Commands
Input Together
Both
the
forward
and
reverse
run
com-
mands
have
been
ON
for
more
than
0.5
s.
-
Check
the
sequence
of
the
forward
and
reverse
run
commands.
Since
the
rotational
direction
is
unknown,
the
motor
will
be
deceler-
ated
to
a
stop
when
this
minor
fault
occurs.
(blink-
ing)
DC
Bus
Under-
volt
Main Circuit Undervoltage
The
following
conditions
occurred
when
there
was
no
Run
signal.
•The
main
circuit
DC
voltage
was
below
the
Undervoltage
Detection
Level
Setting
(L2-05).
•The
surge
current
limiting
contactor
opened.
•The
control
power
supply
voltage
when
below
the
CUV
level.
See
causes
for
UV1,
UV2,
and
UV3
faults
in
the
previous
table.
See
corrective
actions
for
UV1,
UV2,
and
UV3
faults
in
the
previous
table.
(blink-
ing)
DC
Bus
Overvolt
Main Circuit Overvoltage
The
main
circuit
DC
voltage
exceeded
the
overvoltage
detection
level.
200
V
class:
Approx.
400
V
400
V
class:
Approx.
800
V
The
power
supply
voltage
is
too
high.
Decrease
the
voltage
so
it's
within
specifications.
(blink-
ing)
Heatsnk
Over-
temp
Cooling Fin Overheating
The
temperature
of
the
Inverter's
cool-
ing
fins
exceeded
the
setting
in
L8-02.
The
ambient
temperature
is
too
high. Install
a
cooling
unit.
There
is
a
heat
source
nearby. Remove
the
heat
source
The
Inverter
cooling
fan
has
stopped.
Replace
the
cooling
fan.
(Contact
your
dealer.)
(blink-
ing)
Over
Heat
2
Inverter Overheating Pre-alarm
An
OH2
alarm
signal
(Inverter
over-
heating
alarm
signal)
was
input
from
a
multi-function
input
terminal
(S3
to
S7).
-
Clear
the
multi-function
input
termi-
nal's
overheating
alarm
input.
(blink-
ing)
Motor
Over-
heat
1
Motor overheating
E
was
set
for
H3-09
and
the
motor
temperature
thermistor
input
exceeded
the
alarm
detection
level.
The
motor
has
overheated.
Check
the
size
of
the
load
and
the
length
of
the
acceleration,
decelera-
tion,
and
cycle
times.
Check
the
V/f
characteristics.
Check
the
motor
temperature
input
on
terminals
A1
and
A2.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSDRIVE 3G3RV Series and is the answer not in the manual?

Omron SYSDRIVE 3G3RV Series Specifications

General IconGeneral
BrandOmron
ModelSYSDRIVE 3G3RV Series
CategoryInverter
LanguageEnglish

Related product manuals