K
KK
K Settings
for
the
Control
Methods
Autotuning
methods
depend
on
the
control
method
set
for
the
Inverter.
Make
the
settings
required
by
the
con-
trol
method.
nOverview
of
Settings
Make
the
required
settings
in
quick
programming
mode
and
autotuning
mode
according
to
the
following
flow-
chart.
Note If the motor cable changes to 50 m or longer for the actual installation, perform stationary autotuning for the line-to-line resistance only on-
site.
* 1. Use rotational autotuning to increase autotuning accuracy whenever it is okay for the motor to be operated.
* 2. If there is a reduction gear between the motor and PG, set the reduction ratio in F1-12 and F1-13.
Fig 4.3 Settings According to the Control Method
START
YES
V/f control?
A1-02 = 0 or 1)
PG?
Motor cable over
50 m or heavy load possibly
causing motor to stall
or overload?
NO
(Default: A1-02 = 0)
YES
A1-02 = 1
NO
Open-loop vector control (A1-02 = 2)
Set E1-03 and E2-04.
V/f default: 200 V/60 Hz(400 V/60 Hz)
(-E) 200 V/50 Hz (400 V/50 Hz)
Set E1-03, E2-04, and F1-01.
V/f default: 200 V/60 Hz(400 V/60 Hz)
(-E) 200 V/50 Hz (400 V/50 Hz)
NO
YES
YES
NO
END
*2
Control mode selection
OK to operate
motor during autotuning?*1
Rotational autotuning
Stationary autotuning
Stationary autotuning for
line-to-line resistance only