Omron SYSDRIVE 3G3RV Series

Omron SYSDRIVE 3G3RV Series
446 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
P
arameter Tables
5
-
8
9
Note Attach
a
Momentary
Power
Interruption
Compensation
Unit
if
compensation
for
power
interruptions
of
up
to
2.0
seconds
is
required
for
200-V
class
Inverters
with
outputs
of
0.4
to
11
kW.
*If
C6-02
is
set
to
0,
1,
or
F
and
the
initial
value
of
C6-03
and
C6-04
is
2.0
kHz,
the
initial
settings
for
C6-02
are
as
follows:
2:
5.0
kHz,
3:
8.0
kHz,
4:
10 kHz,
5:
12.5
kHz,
and
6:
15
kHz.
If
the
carrier
frequency
is
set
higher
than
the
factory
setting
for
Inverters
with
outputs
of
7.5
kW
or
more,
the
Inverter
rated
current
will
need
to
be
reduced.
Parame-
ter
Num-
ber
Name Unit Factory Setting
- Inverter Capacity kW 160 185 220 300
o2-04 kVA selection - 34 35 36 37
b8-03
Energy-saving
filter
time
constant
s
2.00
(Open
loop
vector
con-
trol)
b8-04
Energy-saving
coeffi-
cient
-
30.13 30.57 27.13 21.76
C6-02
Carrier
frequency
selec-
tion
*
-3311
-
Carrier
frequency
selec-
tion
upper
limit
-4411
E2-01
(E4-01)
Motor
rated
current A
270.0 310.0 370.0 500.0
E2-02
(E4-02)
Motor
rated
slip Hz 1.35 1.30 1.30 1.25
E2-03
(E4-03)
Motor
no-load
current A
70.0 81.0 96.0 130.0
E2-05
(E4-05)
Motor
line-to-line
resis-
tance
0.029 0.025 0.020 0.014
E2-06
(E4-06)
Motor
leak
inductance % 20.0 20.0 20.0 20.0
E2-10
Motor
iron
loss
for
torque
compensation
W
2850 3200 3700 4700
L2-02
Momentary
power
loss
ridethru
time
s 2.0 2.0 2.0 2.0
L2-03
Min.
baseblock
(BB)
time
s 1.8 1.9 2.0 2.1
L2-04 Voltage
recovery
time s 1.0 1.0 1.0 1.0
L8-02 Overheat
pre-alarm
level °C95959595

Table of Contents

Related product manuals