djusting Frequency References
6
-
3
1
nRelated
Parameters
The
following
diagram
shows
the
method
for
adjusting
the
frequency
reference
using
pulse
inputs.
Fig 6.32 Frequency Reference Adjustments Using Pulse Train Inputs
nSetting
example
This
example
results
in
an
output
frequency
of
30
Hz
when
a
2-kHz
pulse
is
input
(maximum
frequency:
60
Hz).
2000
Hz:
30
Hz
=
Set
value:
60
Hz
Set
value
=
2000
x
60/30
=
4000
Hz
(4
kHz)
nSetting
precautions
The
pulse
train
inputs
of
the
Inverter
do
not
control
positioning
as
they
do
for
servomotors
and
stepper
motors.
Speed
control
is
thus
absolutely
necessary.
Make
adjustments
with
the
following
procedure.
1. First,
adjust
the
pulse
train
input
bias
setting.
Adjust
the
output
with
respect
to
the
pulse
input
near
the
minimum
output
frequency.
2. Next,
adjust
the
pulse
train
input
gain
setting.
Adjust
the
output
with
respect
to
the
pulse
input
near
the
maximum
output
frequency.
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control
Methods
V/f
V/f
with
PG
Open
Loop
Vec-
tor
LCD
Display
H6-01
Pulse
train
input
function
selection
0:
Frequency
reference
1:
PID
feedback
value
2:
PID
target
value
0
to
20 NoAAA
Pulse
Input
Sel
H6-02
Pulse
train
input
scaling
Set
the
number
of
pulses
in
Hz,
taking
the
refer-
ence
to
be
100%.
1000
to
32000
1440
Hz Yes A A A
Pulse
In
Scaling
H6-03
Pulse
train
input
gain
Set
the
input
gain
level
as
a
percent
when
the
pulse
train
set
in
H6-02
is
input.
0.0
to
1000.0
100.0% Yes A A A
Pulse
Input
Gain
H6-04
Pulse
train
input
bias
Set
the
input
bias
when
the
pulse
train
is
0.
-100.0
to
100.0
0.0% Yes A A A
Pulse
Input
Bias
H6-05
Pulse
train
input
filter
time
Set
the
pulse
train
input
primary
delay
filter
time
constant
in
seconds.
0.00
to
2.00
0.10
s
Yes A A A
Pulse
In
Filter
RP
Cycle
measurement
Filter
H6
-
05
H6
-
01
Master speed
frequency
PID feedback
PID target value
=0
=2
=1
Scaling using H6-02
Gain and bias
Pulse
1
1+sT
0
H6
-
04
H6
-
03
100

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSDRIVE 3G3RV Series and is the answer not in the manual?

Omron SYSDRIVE 3G3RV Series Specifications

General IconGeneral
BrandOmron
ModelSYSDRIVE 3G3RV Series
CategoryInverter
LanguageEnglish

Related product manuals