onitor Parameters
6
-
7
5
nAdjusting
the
Pulse
Monitor
Items
Adjust
the
pulse
frequency
output
from
pulse
monitor
terminal
MP-SC.
Set
the
pulse
frequency
output
when
100%
frequency
is
output
to
H6-07.
Set
H6-06
to
2,
and
H6-07
to
0,
to
output
the
frequency
synchronous
with
the
Inverter's
U-phase
output.
nApplication
Precautions
When
using
a
pulse
monitor
parameter,
connect
a
peripheral
device
according
to
the
following
load
condi-
tions.
If
the
load
conditions
are
different,
there
is
a
risk
of
characteristic
insufficiency
or
damage
to
other
devices.
Using
a
Sourcing
Output
Output
Voltage
(Iso-
lated)
VRL
(V)
Load
Impedance
(k)
+5
V
min. 1.5
k
min.
+8
V
min. 3.5
k
min.
+10
V
min. 10
k
min.
Load impedance
MP
AC
VRL
Using
a
Sinking
Input
External
Power
Supply
(V)
12
VDC±10%,
15
VDC±10%
Sink
Current
(mA) 16
mA
Max
Load impedance
Sinking current
External power supply
MP
AC