T
erminal
Block
Configuration
2
-
9
Control-circuit
Terminals
(Same
for
200-V
and
400-V
Class)
The
functions
for
the
control-circuit
terminals
by
symbol
are
shown
in
Table
2.2.
Table
2.2
Control-circuit
Terminal
Functions
Type
Signal
Symbol
Signal
Name Terminal
Function Signal
Level
Sequence
Input
S1 Forward-stop
command Forward
when
ON,
stop
when
OFF
+24
VDC,
8
mA
photocoupler
isolation
S2 Reverse-stop
command Reverse
when
ON,
stop
when
OFF
S3 Multi-function
input
selection
1
Factory
setting:
External
fault
detected
when
ON
S4 Multi-function
input
selection
2
Factory
setting:
Fault
reset
when
ON
S5 Multi-function
input
selection
3
Factory
setting:
Multi-step
speed
command
1
effective
when
ON
S6 Multi-function
input
selection
4
Factory
setting:
Multi-step
speed
command
2
effective
when
ON
S7 Multi-function
input
selection
5
Factory
setting:
Inching
frequency
selected
when
ON
SC Sequence
control
input
common -
Analog
Input
+V +15-V
power
supply
+15-V
power
supply
for
analog
ref-
erence
+15
V
(20
mA
maximum
allowable
current)
A1 Main
speed
frequency
reference 0
to
10
V/100%
0
to
10
V
(input
imped-
ance:
20
k)
A2 Multi-function
analog
input
4
to
20
mA/100%,
0
to
10
V/100%
Factory
setting:
Add
to
terminal
A1
(H3-09
=
0)
4
to
20
mA
(input
imped-
ance:
20
kΩ)
0
to
10
V
(input
imped-
ance:
20
k)
AC Analog
common 0
V-
E
(G)
Shield
wire,
optional
ground
con-
nection
--
Sequence
Output
P1 Multi-function
output
1
Factory
setting:
Zero
speed
Zero
level
(b2-01)
or
below
when
ON.
Open
collector
output
+48
VDC,
50
mA
P2 Multi-function
output
2
Factory
setting:
Frequency
agree-
ment
detection
ON
when
the
frequency
is
within
±2 Hz
of
the
set
frequency.
PC Photocoupler
output
common -
MA Fault
output
(NO
contact) ON
between
MA
and
MC
during
fault
ON
between
MB
and
MC
during
fault.
Relay
output
Dry
contacts
Contact
capacity
250
VA C ,
1
A
max.
30
VDC,
1
A
max.
MB Fault
output
(NC
contact)
MC Relay
contact
output
common -
M1
Multi-function
output
(NO
con-
tact)
Factory
setting:
RUN
ON
between
M1
and
M2
during
operation.
M2
Analog
Monitor
Output
FM Multi-function
analog
monitor
1
Factory
setting:
Output
frequency
0
to
10
V/100%
frequency
0
to
+10
VDC
±5%
2
mA
max.AM Multi-function
analog
monitor
2
Factory
setting:
Current
monitor
5
V/Inverter
rated
current
AC Analog
common -
Pulse
Input/Out-
put
RP Multi-function
pulse
input
Factory
setting:
Frequency
refer-
ence
input
(H6-01
=
0)
0
to
32
kHz
(3
kΩ)
MP Multi-function
pulse
monitor
Factory
setting:
Output
frequency
(H6-06
=
2)
0
to
32
kHz
(2.2
kΩ)