2
-
12
Control-circuit
Terminals
(Same
for
200-V
and
400-V
Class)
The
functions
for
the
control-circuit
terminals
by
symbol
are
shown
in
Table
2.5.
Table
2.5
Control-circuit
Terminal
Functions
Type
Signal
Symbol
Signal
Name Terminal
Function Signal
Level
Sequence
Input
S1 Forward-stop
command Forward
when
ON,
stop
when
OFF
+24
VDC,
8
mA
photocou-
pler
isolation
S2 Reverse-stop
command Reverse
when
ON,
stop
when
OFF
S3 Multi-function
input
selection
1
Factory
setting:
External
fault
detected
when
ON
S4 Multi-function
input
selection
2
Factory
setting:
Fault
reset
when
ON
S5 Multi-function
input
selection
3
Factory
setting:
Multi-step
speed
command
1
effective
when
ON
S6 Multi-function
input
selection
4
Factory
setting:
Multi-step
speed
command
2
effective
when
ON
S7 Multi-function
input
selection
5
Factory
setting:
Inching
frequency
selected
when
ON
SC Sequence
control
input
common -
SP
Isolation
power
supply
for
sequence
input
+24
V
-
+24
VDC
±20%
SN
Isolation
power
supply
for
sequence
input
0
V
-
Analog
Input
+V +15-V
power
supply
+15-V
power
supply
for
analog
reference
+15
V
(20
mA
maximum
allowable
current)
-V -15-V
power
supply
-15-V
power
supply
for
analog
reference
-15
V
(20
mA
maximum
allowable
current)
A1 Main
speed
frequency
reference 0
to
+10
V/100%
0
to
+10
V
(input
imped-
ance
20
kΩ)
A2 Multi-function
analog
input
4
to
20
mA/100%,
0
to
+10
V/100%
Factory
setting:
Add
to
terminal
A1
(H3-09
=
0)
4
to
20
mA
(input
imped-
ance
20
kΩ)
0
to
+10
V
(input
imped-
ance
20
kΩ)
AC Analog
common 0
V-
E
(G)
Shield
wire,
optional
ground
con-
nection
--
Sequence
Output
MA Fault
output
(NO
contact) ON
between
MA
and
MC
during
fault
ON
between
MB
and
MC
during
fault
Relay
output
Dry
contacts
Contact
capacity
250
VAC,
1
A
max.
30
VDC,
1
A
max.
MB Fault
output
(NC
contact)
MC Relay
contact
output
common -
M1
Multi-function
contact
output
(NO
contact)
Factory
setting:
RUN
ON
between
M1
and
M2
during
operation
M2
M3
Multi-function
output
1
Factory
setting:
Zero
speed
Zero
level
(b2-01)
or
below
when
ON
M4
M5
Multi-function
output
2
Factory
setting:
Frequency
agree-
ment
detection
ON
when
the
frequency
is
within
±2
Hz
of
the
set
frequency
M6
Analog
Monitor
Output
FM Multi-function
analog
monitor
1
Factory
setting:
Output
frequency
0
to
+10
V/100%
frequency
0
to
+10
VDC
±5%
2
mA
max.AM Multi-function
analog
monitor
2
Factory
setting:
Current
monitor
5
V/Inverter
rated
current
AC Analog
common -

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSDRIVE 3G3RV Series and is the answer not in the manual?

Omron SYSDRIVE 3G3RV Series Specifications

General IconGeneral
BrandOmron
ModelSYSDRIVE 3G3RV Series
CategoryInverter
LanguageEnglish

Related product manuals