The following instructions cannot be used in block programs.
Group Mnemonic Remarks
Bit control
ii
DIFU(013)
---
instructions
DIFD(014)
KEEP(011)
OUT
Use SET(016) and RSET(017). (There are
not block SET and RSET instructions for
OUT NOT
no
t
bl
oc
k
SET
an
d
RSET
i
ns
t
ruc
ti
ons
f
or
CV-series PCs.)
Interlock and
j
IL(002)
---
jump
instructions
ILC(003)
i
nstruct
i
ons
JMP(004) 0000
These instruction can be used if the PC
Si h lilj ihj
CJP(221) 0000
Setup is set so that multiple jump with jump
number 0000 cannot be used
CJPN(222) 0000
num
b
er
0000
cannot
b
e use
d
.
JME(005) 0000
END END(001) Use BEND<001>.
Timer and
TIM
Use the block programming timer and counter
ii
counter
instructions
CNT
gg
instructions.
i
nstruct
i
ons
TIMH(015)
TTIM(120)
---
TIML(121)
MTIM(122)
CNTR(012)
Step
ii
STEP(008)
---
instructions
SNXT(009)
Shift
instructions
SFT(050) ---
Subroutine
ii
SBN(150)
---
instructions
RET(152)
Diagnostic
instructions
FPD(177) ---
PID and related
instructions
PID(270) ---
Special I/O Unit
ii
RD2(280)
---
instructions
WR2(281)
Differentiated
instructions
--- No input differentiated instructions () can be
used in block programs.
5-38-2 BLOCK PROGRAM BEGIN/END: BPRG(250) / BEND<001>
(250)
BPRG N
N: Block program number # (00 to 99)
Operand Data AreaLadder Symbol
BEND<001>
BPRG(250) is used to switch to block programming and BEND<001> is used
to switch back to ladder-diagram programming. For every BPRG(250) there
must be a corresponding BEND<001>. The corresponding block program will
be executed with the execution condition for BPRG(250) is ON and it will be
skipped (not executed) when the execution condition is OFF.
Description
(CVM1 V2)
Block Programming Instructions Section 5-38