EasyManua.ls Logo

Omron SYSMAC CV Series - 7-3 PC Setup Default Settings

Omron SYSMAC CV Series
636 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
490
The PC takes longest to respond when the Master receives the input signal just
after I/O refreshing. This situation is illustrated below.
Input signal
Output signal
Cycle
Cycle time
I/O refresh
I/O response time
Output ON delay
Input ON delay
Buffer in Master
Transmission time
T
RM
AB AB AB AB
A: Program execution
B: Peripheral servicing
Maximum I/O response time = input ON delay + cycle time x 2
+ Master transmission time x 2 + Slave transmission time x 2
+ output ON delay
Maximum I/O response time = 1.5 + (20×2) +(8.2×2) +(2.2×2) +15 = 77.3 ms
6-5-4 Asynchronous Operation with a SYSMAC BUS/2 System
Here, we’ll compute the minimum and maximum I/O response times for a
CV1000 that is set for asynchronous operation and controls a SYSMAC BUS/2
System. Both the input and output are on I/O Units connected to Slave Racks. In
asynchronous operation, SYSMAC BUS/2 refreshing occurs at the end of the
SYSMAC BUS/2 communications cycle.
This calculation only applies when the SYSMAC BUS/2 Master is the only CPU
Bus Unit connected to the CPU. If other CPU Bus Units are connected, add the
following delay to the maximum I/O response time calculated later in this sec-
tion: (other Unit’s refreshing time +1.5 ms)×(number of CPU Bus Units con-
nected)
If a higher priority peripheral process such as a SEND(192), RECV(193), or
FAL(006) instruction occurs, it will be processed before the SYSMAC BUS/2
servicing, increasing the I/O response time.
Maximum I/O Response
Time
I/O Response Time Section 6-5

Table of Contents

Related product manuals