QG-25
QG-32
QG-40
GENERATOR
MODEL NO.
MAX. POWER
OUTPUT (kW)
NOMINAL LINE
VOLTAGE (VAC)
DISCONNECT
TO GENERATOR
15 FT. (5 M) MAX.
*SERVICE
RATING
*RECOMMENDED
DISTRIBUTION
TRANSFORMER
CAPACITY
MAX. INPUT LINE
RESISTANCE
(AT FULL-LOAD
RMS)
NOTE: All installations must meet the requirements of local electrical codes.
The above values are recommended as typical (unless otherwise specified).
*
1.
±5%)
Line Regulation: 5% at full load.
7. Ground wire size is 4 AWG.
8. Specifications are subject to change.
9. Specifications for single-phase “stored energy” Models QG-20-SE, QG-32-SE,
QG-40-SE and QG-50-SE are as follows:
105-130 VAC (±10%), 10 Amps, 50/60 Hz
210-250 VAC (±10%), 10 Amps, 50/60 Hz
All wire must be copper.
2. Actual wire size depends on power quality and distance between mains power
and the generator.
3. All wiring and grounding must be in accordance with National
Electric Code (NFPA #70) or local electrical codes.
4. The disconnect switch must be located within reach of the operator.
5. Input Voltage: 208-257 ( VAC 50/60 Hz (configured at time of installation).
6.
QG-250
QG-320,
QG-3200,
QGV-32
QG-400,
QG-4000,
QGV-40
GENERATOR
CATALOG NO.
208
25
32
40
240
208
240
208
240
#4 AWG
#4 AWG
#2 AWG
#2 AWG
#1 AWG
#1 AWG
100 AMPS
80 AMPS
120 AMPS
100 AMPS
150 AMPS
120 AMPS
30 KVA
30 KVA
40 KVA
40 KVA
50 KVA
50 KVA
0.06 OHMS
0.08 OHMS
0.04 OHMS
0.05 OHMS
0.035 OHMS
0.04 OHMS