Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
196 Operating Instructions, 06/2018, A5E36281317-AC
Relay set off, no action (preset).
Level Based on level setpoints ON and OFF.
Alarm
General In-bounds When level enters the range between ON and
Out-of-bounds When level exits the range between ON and
Based on rate setpoints ON and OFF.
Based on temperature setpoints ON and OFF.
Loss of echo; when echo is lost.
When the circuit to a transducer is opened.
Flow Totalizer Every 10
y
units [Mantissa (2.10.2.2.)
(Page 213) - Relay Duration (2.10.2.4.)
Flow Sampler Every y x 10
2
units [Mantissa (2.10.2.2.)
(Page 213) - Relay Duration (2.10.2.4.)
(Page 215)] or time duration [Relay Interval
Setpoint (2.10.2.6.) (Page 215)]
Pump Fixed Duty Assist At fixed ON and OFF setpoints and allows
multiple pumps to run or for rake control.
Fixed Duty Backup At fixed ON and OFF setpoints and allows only
Alternate Duty Assist At rotating ON and OFF setpoints and allows
Alternate Duty Backup At rotating ON and OFF setpoints and allows
Service Ratio Duty Assist On service ratio at ON and OFF setpoints and
allows multiple pumps to run.
Service Ratio Duty Backup On service ratio at ON and OFF setpoints and
allows only one pump to run.
First In First Out As Alternate Duty Assist, resets the relay from
Control Flush Valve Used to control a pump flushing device based
on Flush Systems [Flush pump (2.10.3.2.)
(Page 216) to Flush duration (2.10.3.5.)
Communication Based on input from external communications.
For more information, see Modbus register