SIMATIC – ET 200pro motor starter
GWA 4NEB 950 5661-02 DS 04
8-11
Blocking current limit value
1)
150% ... 1000% I
e
,
with soft starter only 800%
800% Module
Blocking time limit value
1)
1s ... 5s 1s Module
Type of start-up • direct
• Voltage ramp
• Current limitation
• Voltage ramp and current limita-
tion
Voltage ramp and
current limitation
Type of run-down • free run-down
• Voltage ramp
free run-down Module
Current limit • 0.15 A - 9 A 0 - 600 %
• 9 A - 12 A 0 - 550 %
600% Module
Startup time 0 s ... 120 s 20 s
Run-down time 0 s ... 120 s 0 s
Start voltage 4 ... 20 8
Stop voltage 4 ... 18 8
Response to CPU / Master
STOP
• Switch substitute value
• Retain the last value
Switch substitute
value
Module
General warning diagnosis
1)
• Disable
• Enable
Enabled Module
Group diagnosis • Disable
• Enable
Disable Module
Digital inputs
1)
• Signal
•Level
• Signal delay
• Signal extension
•Action
only make contact
only make contact
only make contact
only make contact
4 inputs
•Latching
• Not latching
• Break contact
• Make contact
10 ms ... 80 ms
0 s ... 200 ms
• No action
• Trip without restart
• Trip with restart
• Tripping end position clockwise
• Tripping end position counter-
clockwise
• General warning
• Operating mode 'Manual opera-
tion local'
• Emergency start
• Motor CLOCKWISE
• Motor COUNTER-CLOCKWISE
• Quick stop
• Trip reset
Not latching
Make contact
10 ms
0s
No action
Module
400 V brake output
3)
• Brake release delay
• Hold time on stopping
–2.5 s ... 2.5 s
0 s ... 25 s
0s
0s
Module
1) only for high feature motor starters
2) of the rated operating current
3) order option
Parameters
Action,
value range
Factory setting
Applica-
bility
Table 8-2: Parameters for motor starters DSe, RSe (standard and high feature); sDSSte / sDSte, sRSSte / sRSte
(cont.)