Motor starter fault types
Motor starters Fault type Meaning / cause Remedy
Direct starter
DSe, sDSSte /
sDSte
Reversing starter
RSe, sRSSte /
sRSte
00100:
Overload
(F4)
Thermal motor model
overload
Let motor cool down
Check current consumption of
the motor
Check set current limits
0 0111 :
Upper limit value
exceeded (F7)
•I
e
- Upper current limit
exceeded
01000:
Lower limit value
undershot
(F8)
•I
e
lower current limit
undershot
01001:
Error
(F9)
Internal error / device
error
Switching element
defective
Switch the supply voltage 1L+ off /
on; if error still present, replace
motor starter.
110 0 0 :
actuator tripping
(F24)
Asymmetry
Motor blocking
Residual current
detected
or in conjunction with
another error type
from this table
Check phases L1 to L3.
Remove blocking.
Check main power lines L1 to L3
for interruption.
11010:
external error
(F26)
Input tripping
Input tripping – end
position
Remove external error (e.g. move
out of end position)
00101
Overload
switching element
(F5)
Thermal motor model
has a load > 178%.
Tripping takes place
as device protection
with parameter "Ther-
mal motor model"
= warning.
Check system configuration
10001:
(F17)
Supply voltage for
switching element
missing
Check 2L+
Table 4-3: Motor starter fault types