SIMATIC - ET 200pro motor starter
4-12 GWA 4NEB 950 5661-02 DS 04
4.6.2 Process image for motor starter
Input signals
DI 0.0 Ready (Automatic) DI 1.0 Motor current I
pres
2)
0 Starter not ready via
host / PLC
Bit 0
1 Starter ready for operation via
host
DI 0.1 Motor on
1)
DI 1.1 Motor current I
pres
2)
0Off Bit1
1 On (clockwise/counterclock-
wise rotation)
DI 0.2 General fault
(short circuit / overload)
DI 1.2 Motor current I
pres
2)
(The occurrence of one or
more errors as described in
Table 4-6 leads to "General
fault" being set, independently
of whether the parameter
"Group diagnosis" (see Chapter
7. 6 . 1 and Chapter 8.2.4) has
been set to "disable" or
"enable".)
Bit 2
0 No error
1Error
DI 0.3 General warning DI 1.3 Motor current I
pres
2)
0No warning Bit3
1Warning
DI 0.4 Input 1 DI 1.4 Motor current I
pres
2)
0 Not active Bit 4
1Active
DI 0.5 Input 2 DI 1.5 Motor current I
pres
2)
0 Not active Bit 5
1Active
DI 0.6 Input 3 DI 1.6 Operating mode 'Manual opera-
tion local'
0 Not active 0 Not active
1 Active 1 Manual operation local
DI 0.7 Input 4 DI 1.7 Ramp operation
(for soft starter)
0 Not active 0 Not active
1Active 1Active
1 ) Signal is 1 if the motor current > 18.75% of the set rated current
2) see Chapter 10.3.1
Parameter description, see Chapter 10.3