SIMATIC – ET 200pro motor starter
GWA 4NEB 950 5661-02 DS 04
4-17
Device diagnosis
In the input process image of the starters, and general faults (DI 0.2) and gen-
eral warning signals that are present (DI 0.3) are transferred in cycles.
If required, more detailed information on the defect type is accessible by calling
up the diagnosis (V1 system diagnosis).
All device-specific diagnoses are grouped in data record 92 (29 bytes). The con-
tents of data record 92 can be read using 'Motor Starter ES' via the device inter-
face or also online via DP V1 using the function 'read data record'.
4.7 Software 'Motor Starter ES'
Features
The diagnosis and commissioning tool 'Motor Starter ES' (version 2006 or
higher) provides you with:
A structured, tool-supported project planning (configuration) of low-voltage
switchgears
Rapid diagnosis
Commissioning and monitoring on site such as:
Parameterization of the control system and guidance system during operation
Monitoring
Diagnosis and test
•Factory setting
Reading out individual phase currents as direct values
Residual current detection
Setting a parameterization lock
Integrated online help
Reading out statistics and measured values