2-6 GWA 4NEB 950 5661-02 DS 04
2.5 Cabling and connecting
Perform the following steps:
1.
Caution
Make sure that the entire configuration has adequate short circuit and overload
protection.
2. Wire up the ET 200pro as shown in Figure 2-3. Only the external cables
shown in bold are still to be connected. These are:
AC 400 V and PE (supply voltage) to connection X1 of the maintenance
isolating module
Consumer units (motors) to connection X2 of the motor starter
Power jumper between connection X3 of the maintenance switch and
connection X1 of the motor starter
The two switches for ON (make contact) and OFF (break contact) on
the electronics module 8 DI DC 24 V
3. Close off connection X2 of the maintenance isolating module with a sealing
cap
4. Close off
connection X3 of the motor starter with a sealing cap
5. Use the PROFIBUS bus connection cable to connect the DP master to the
ET 200pro. The PROFIBUS DP interface is located on the
IM 154-. DP high feature.
6. Switch on the voltage supply for the DP master.
7. Observe the status LEDs on the DP master.
CPU 315-2 DP:
- DC 5 V green
- SF DP off
- BUSF flashes red