EasyManua.ls Logo

Siemens SIMATIC ET 200pro - 9.2 Cutting power cables to length

Siemens SIMATIC ET 200pro
260 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connecting
SIMATIC – ET 200pro motor starter
GWA 4NEB 950 5661-02 DS 04
9-3
9.2 Cutting power cables to length
9.2.1 To cut power cables to length, you require:
For assembly of the sockets and pins on the individual wires, a crimping tool
(see Chapter A.2).
As well as the following accessories:
For infeed to special modules (assignment of X1, see Chapter 9.2.2),
for infeed to motor starters (assignment of X1, see Chapter 9.2.3):
A flexible Cu cable with 4 x 2.5 mm
2
/ 4 mm
2
/ 6 mm
2
(3-wire + PE)
A power plug connector HAN Q4/2 socket
- for 2.5 mm
2
: 3RK1911-2BE50
- for 4.0 mm
2
: 3RK1911-2BE10
- for 6 mm
2
: 3RK1911-2BE30
For power loop-through to the special modules RSM and F-RSM
(assignment of X2, see Chapter 9.2.2):
A flexible Cu cable with 4 x 2.5 mm
2
/ 4 mm
2
/ (3-wire + PE)
A power plug connector HAN Q4 / 2-pin
- for 2.5 mm
2
: 3RK1911-2BF50
- for 4.0 mm
2
: 3RK1911-2BF10
For consumer unit connection to the motor starter
(assignment of X2, see Chapter 9.2.3):
A flexible Cu cable with 1.5 mm
2
or 2.5 mm
2
- without brake control: 3-wire + PE
- with brake control: 5-wire + PE
A power plug connector HAN Q8/0 pin
- for 1.5 mm
2
: 3RK1902-0CE00
- for 2.5 mm
2
: 3RK1902-0CC00
Figure 9-1: Example: Power infeed
SF
BF
ON
DC 24V
MSMS
Connector set
7-pin (socket)
angled cable routing
Energy infeed
MM