SIMATIC – ET 200pro motor starter
GWA 4NEB 950 5661-02 DS 04
10-19
10.5.2 Device parameters for asymmetry – settings
The following table shows the settings of the device parameters:
10.5.3 Signals, actions and measured values
The device function 'Asymmetry' delivers the following signals and actions:
Signals, actions
Measured values
10.6 Trip reset
'Trip reset' acknowledges all of the currently pending faults in the starter that
can be acknowledged. A fault can be acknowledged when it has been remedied
or is no longer pending.
The trip reset can be triggered by:
• the user application via the process image DO 0.3
• the local device interface with the software 'Motor Starter ES'
Device parameters Default Adjustment range
Response to asymmetry Tripping Warning / Tripping
Asymmetry limit value 30% 30% to 60%
Increment: 10%
Table 10-10: Device parameters for asymmetry – settings
Signal Action
Asymmetry detected —
Asymmetry tripping Tripping (asymmetry present)
Table 10-11: Asymmetry – signals and actions
Measured values Description
Asymmetry Asymmetry 0 to 100%
Increment: 1%
Table 10-12: Asymmetry – measured values