Data formats and data records
SIMATIC – ET 200pro motor starter
GWA 4NEB 950 5661-02 DS 04
D-7
D.3.2 Data record 69 – read process image of the inputs
Byte Meaning
Process image of the inputs
0 Process data DI 0.0 to DI O.7, table below
1 Process data DI 1.0 to DI 1.7, table below
2 Reserved = 0
3 Reserved = 0
ID no. Process data Process image 1:
(8 E, DI 0.0 to DI 0.7)
Process image 2:
(16 E, DI 0.0 to DI 1.7)
1101 DI 0. 0 Ready (Automatic) Ready (Automatic)
1102 1 Motor on Motor on
1103 2 Group error Group error
1104 3 General warning General warning
1105 4 Input 1 Input 1
1106 5 Input 2 Input 2
1107 6 Input 3 Input 3
1108 7 Input 4 Input 4
110 9 DI 1. 0 — Motor current I
pres-bit0
1110 1 — Motor current I
pres-bit1
1111 2 — M o t o r c ur re nt I
pres-bit2
1112 3 — Motor current I
pres-bit3
1113 4 — Motor current I
pres-bit4
1114 5 — Motor current I
pres-bit5
1115 6 — Operating mode 'Manual
operation local'
1116 7 — Ramp operation
Table D-3: Data record 69 – read process image of the inputs