SIMATIC – ET 200pro motor starter
GWA 4NEB 950 5661-02 DS 04
3-1
Installation 3
3.1 Installation rules
Installing the wide module holder
For assembly of the wide module holder, please consult the manual 'Decentral-
ized peripheral device ET 200pro'.
On assembly, observe the following:
Maximum permitted length: 1 m
A maximum of 8 motor starter modules can be operated on one ET 200pro inter-
face module
Easy installation
The decentralized peripheral system ET 200pro is designed for simple installa-
tion.
ET 200pro motor starters are set up as complete devices together with a rear
wall bus module (110 mm) on a wide module holder (extruded profile).
First of all, mount the ET 200pro interface module IM 154-. on the module
holder. Then snap the desired rear wall bus modules one after the other into
place on the right of the interface module IM 154-.
The function modules are assembled on the rear wall bus module in the same
way by placing them to the right of the interface module IM 154-. or on the pre-
vious module by snapping on and then screwing them firmly down with 3 Phil-
ips screws.