SIMATIC - ET 200pro motor starter
10-38 GWA 4NEB 950 5661-02 DS 04
10.15 Control function reversing starter
Description
This control function enables the RSe motor starter to control the motor direc-
tion. The internal logic prevents both contactors from pulling in simultaneously.
Time-delayed switching from one motor direction to the other is enabled by
means of the lock-out time.
10.15.1 Device parameters
Lock-out time (can only be parameterized for high feature motor starters)
The 'lock-out time' delays switching the direction of rotation. The flywheel of a
drive must come to a standstill within the lock-out time before the next switch-
ing command is executed.
Setting range: 0 to 60 seconds
Caution
A lock-out time of 0 means 150 milliseconds for safety reasons.
10.15.2 Device parameters – settings
The following table shows the settings of the device parameters:
10.15.3 Signals
The control function reversing starter delivers the following signals:
Device parameters Default Adjustment range
Lock-out time 0 0 to 60 seconds Incre-
ment: 1 sec. (only for
RSe HF)
Table 10-25: Device parameters for control function reversing starter – settings
Signal
Motor COUNTER-CLOCKWISE:
Lock-out time active
Table 10-26: Control function reversing starter – signals